Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2006 | ELECTRIC - SERVICE UPGRADE | Cancelled | IVRS - RI canceled | |
| 11/21/2006 | ELECTRIC - SERVICE UPGRADE | Approved | CALL FOR FINAL ONCE CHANGED OVER | |
| 11/16/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SECURE MAST BRACE INTO STRUCTURE NOT ROOF SHEATHING. 2. USE THREADED CONNECTION FOR BRACE NOT EMT CONNECTOR. 3. MAKE SURE BRACE POINTS IN THE DIRECTION OF THE SERVICE DROP - SO IT IS EFFECTIVE. 4. BURY GROUND MINIMUM 12" AND TIGHTEN ACORNS. |