Permit: T06EL01399

Parcel: 11520106A


Addresses:

1915 W RIVERVIEW ST

Inspection Status: Cancelled

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/21/2006 ELECTRIC - SERVICE UPGRADE Cancelled IVRS - RI canceled
11/21/2006 ELECTRIC - SERVICE UPGRADE Approved CALL FOR FINAL ONCE CHANGED OVER
11/16/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
1. SECURE MAST BRACE INTO STRUCTURE NOT ROOF SHEATHING.
2. USE THREADED CONNECTION FOR BRACE NOT EMT CONNECTOR.
3. MAKE SURE BRACE POINTS IN THE DIRECTION OF THE SERVICE DROP - SO IT IS EFFECTIVE.
4. BURY GROUND MINIMUM 12" AND TIGHTEN ACORNS.