Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE COPPER AND ALUMINUM SPLICED UNDER SAME LUG IN METER CAN. 2. BOND WIRE PENETRATES ROOF FLASHING 3. BOND CLAMP FOR GAS IS LOOSE AND DETERIORATED 4. PANEL ENCLOSURE NOT BONDED |