Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SUB-PANEL ON WESTSIDE OF HOUSE NEEDS GROUND BAR FOR GROUNDS -- DO NOT COMBINE NEUTRALS & GROUNDS. |
|
| 07/21/2006 | ELECTRIC - FINAL | Denied | 1. THIS HOUSE HAS AN ELECTRICAL SYSTEM WHICH HAS NO GROUND -- ALL RECEPTACLES SHOULD ONLY BE 2 HOLE NOT 3 2. SERVICE HAS ONE 60 AMP. BREAKER MARKED SUB-PANEL AND ONE MAKE 100 AMP. -- COULD ONLY FIND ONE IN HOUSE SO YOU KNOW WHERE OTHER ONE IS? |