Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE PROPER BOXES AND CONNECTORS FOR CONNECTION OF RACEWAY. 2. EMT NOT ALLOWED UNPROTECTED IN EARTH. 3. USE PROPER ROMEX CONNECTORS TO METAL BOXES. 4. HAVE TRENCH OPEN FOR INSPECTION. 5. GROUND ALL METAL BOXES. 6. INSTALL NAIL PLATES AS NEEDED. 7. STAPLE ROMEX WITHIN 8" OF BOXES 8. STRAP RACEWAYS WITHIN 3' OF BOXES. 9. NEED MUD RING ON BOX INSIDE WALL. 10. NEED A LISTED FAN BOX FOR CEILING FAN. |