Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL01356

Parcel: 12313101A


Addresses:

2110 N 1ST AV #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/28/2006 ELECTRIC - FINAL Approved
07/26/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. ADD A UNISTRUT BAR BETWEEN TWO RISERS AT TOP POINT WHERE KICKER'S TIED TO 2" CONDUIT AND STRAP.
2. TAPE ENTIRE SHOWN LENGTH OF GREEN WIRE USED IN J-BOXES AND IN SERVICES WHITE. THESE ARE NEUTRALS.

CALL BACK FOR CLEARANCE.