Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEE NOTE #1 2. SUPPORT CABELING IN TRUSSES IN NORTHWEST AREA OF WAREHOUSE. |
|
| 07/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPAIR/REPLACE ALL CRACKED DEVICES AND DEVICE COVERS. 2. INSTALL COVERS AND K.O BLANKS ON ALL OPEN WIRING THROUGHOUT BUILDING. 3. DOCK HAS OPEN WIRING AND OPEN BREAKER SPACES. 4. INTERIOR PANEL HAS DOUBLE BRANCH CKT'S ON BREAKERS, RACEWAY INTO PANEL NOT COMPLETE. 5. CHECK EMERGENCY LIGHTING BATTERIES TO MAKE SURE THEY WORK. |