Permit: T06EL01350

Parcel: 127033450


Addresses:

5513 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/26/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/25/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WHAT IS NAMEPLATE RATING OF DRYER? IS 20 AMPS LARGE ENOUGH TO HANDLE LOAD?
2. CONNECT #10 TO GROUND SPLICE NOT JUST ENCLOSURE.
07/24/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. TIGHTEN LOOSE FITTINGS
2. MOUNTING BOLT NOT FOR GROUNDING AND CLEAN SURFACE UNDER GROUND LUG.
3. GROUNDING CONDUCTOR TO BE SIZED PER 250.122
4. PLEASE VERIFY DERATING PER 310.15
5. RISE HARDWARE TO BE 1/4" MINIMUM