Permit: T06EL01347

Parcel: 12218019A


Addresses:

3844 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/01/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CONTRACTOR STATES NO PERMITS FOR WORK TO INTERIOR
2. MIKE KISER FROM TEP TO VERIFY IF COMMERCIAL REQUIREMENTS ARE NEEDED.
3. THERE ARE NEW THHN CONDUCTORS LEADING PANEL FROM BREAKER MARKED FUSE BOX NEED TO SEE TERMINATION OF NEW CONDUCTORS.

* I OBSERVED NEW MC CABLE AND 4 SQ. BOXES ON INTERIOR.
07/28/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLEASE VERIFY PERMITS FOR WORK TO INTERIOR.
2. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8
3. WHERE IS WATER & GAS BOND CONNECTIONS
4. IS THIS A RESIDENCE OR COMMERCIAL PROPERTY. SERVICE REQUIRMENT FOR TEP DIFFER.
5. NEED TO SEE CONNECTION OF NEW CONDUCTORS TO FUSE BOX.