Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/25/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/24/2006 | ELECTRIC - SERVICE UPGRADE | Denied | YOUR SPLICES IN J-BOX HAVE TO BE TAPED THOROUGHLY I CAN SEE OPEN PARTS OF METAL, THIS IS A PROBLEM WHICH NEEDS TO BE TAKEN CARE AS SOON AS POSSIBLE -- PLEASE CORRECT & RECALL CALL ME IF ANY QUESTIONS. |
|
| 09/19/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. STILL NEED TO CORRECT #1, #2, AND 3 FROM PREVIOUS INSPECTION. 2. NEED PROTECTIVE BUSHING FOR #4 WIRE ENTERING J-BOX 3. SELF TAP SCREW NOT ALLOWED FOR GROUND LUG @ J-BOX AND REMOVE PAINT FROM BEHIND LUG. THERE WILL BE A REINSPECTION FEE CHARGED IF NOT ALL CORRECT ON NEXT INSPECTION. *NOTE: GROUND RODS TO BE FLUSH WITH OR BELOW GRADE. |
|
| 09/07/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BOND WATER AND GAS PIPES TO SERVICE 2. WHY ARE GROUND RODS TO FAR FROM SERVICE? MOVE CLOSER IF ABLE 3. READ INSTRUCTIONS FOR OVERHEAD SERVICE HOOKUP IN METER SECTION AND MOVE ACCORDINGLY SERVICE WIRE/TERMINALS TO MOVE TO TOP 4. SECURE GROUNDING ELECTRODE CONDUCTOR TO HOUSE WHERE IT GOES DOWN THE WALL. 5. SECURE SERVICE TO STRUCTURE -- BACK WOOD IS LOOSE |