Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01325
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUNDING ELECTRODE TO BE AS CLOSE AS POSSIBLE 2) ENTRANCE ABOVE CURRENT CARRING PARTS TO BE SPACED 3) USE APPROVED FITTING WITH LB 4) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGED INTO 406.8 5) SUPPORT CONDUITS OUT OF PANEL 6) BOND INTERIOR SIDE OF WATER VALVE 7) BOND GAS 8) RECEIVED CHECK #7637 FOR $108.00 UNSCHEDULED INSPECTION |