Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06EL01325

Parcel: 122091120


Addresses:

1710 N LOUIS LN


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL01325

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
07/14/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) GROUNDING ELECTRODE TO BE AS CLOSE AS POSSIBLE
2) ENTRANCE ABOVE CURRENT CARRING PARTS TO BE SPACED
3) USE APPROVED FITTING WITH LB
4) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGED INTO 406.8
5) SUPPORT CONDUITS OUT OF PANEL
6) BOND INTERIOR SIDE OF WATER VALVE
7) BOND GAS
8) RECEIVED CHECK #7637 FOR $108.00 UNSCHEDULED INSPECTION