Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUNDING ELECTRODE TO BE AS CLOSE AS POSSIBLE 2) ENTRANCE ABOVE CURRENT CARRING PARTS TO BE SPACED 3) USE APPROVED FITTING WITH LB 4) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGED INTO 406.8 5) SUPPORT CONDUITS OUT OF PANEL 6) BOND INTERIOR SIDE OF WATER VALVE 7) BOND GAS 8) RECEIVED CHECK #7637 FOR $108.00 UNSCHEDULED INSPECTION |