Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/20/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CLEAN SURFACE UNDERGROUND BAR IN JUNCTION BOX 2. PLEASE IDENTIFY CIRCUITS TO VERIFY PHASING FOR SHARED NEUTRALS. 3. LABEL CIRCUIT BREAKERS 4. VERIFY DERATING OF CONDUCTORS 310.15 |