Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/13/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. PLUG UNUSED OPENINGS IN PANEL AT SERVICE. 2. UNSUPPORTED CONDUIT & EXPOSED WIRING OUTSIDE EAST WALL. 3. UNSUPPORTED ROMEX, IMPROPER ROMEX CONNECTIONS & SPLICES UNDER CARPORT. 4. J-BOXES ON ROOF NOT WEATHERPROOF. MUST BE RATED FOR OUTDOOR USE. 5. PLUG UNUSED OPENING AT J-BOX OUTSIDE NORTH WALL, OUTSIDE RECEPT. TO BE GFI AT VOLLEYBALL COURT. ALSO, REPLACE COVER AT J-BOX 6. CARPORT DOORWAY WALL LTS MISSING 7. SUPPORT J-BOXES WIRING AT BAPTISMAL AREA. |