Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06EL01302
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
07/26/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/25/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* PARTIAL INSPECTION FOR SERVICE ONLY 1. BOND SERVICE RISER RACEWAYS -- NEC 250.92 2. BOND CT ENCLOSURE -- NEC 250.92 3. SERVICE NEUTRALS APPEAR TO BE UNDERSIZED -- NEC 250.24 (B)(1) 4. BONDING JUMPERS TO SERVICE NIPPLES ARE UNDERSIZED NEC 250.102 (C) 5. TIGHTEN ALL GROUNDING FITTINGS/SET SCREWS -- NEC 110 6. SECURE SERVICE TO STRUCTURE -- NEC 110 7. GROUNDING ELECTRODE CONDUCTOR IS SPLICED INCORRECTLY -- NEC 250.64(C) AND UNDERSIZED PER EXISTING CONDUCTOR SIZE. 8. PROVIDE APPROVED PLANS AS NEEDED - 2 - 750 AS PER PHASE #1 CU BOND #2/0 AL NEUT (2) 800 AMP 9. BOND INTERIOR METAL PIPING TO SERVICE -- NEC 250.104 |