Permit: T06EL01302

Parcel: 10825020C


Addresses:

2000 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06EL01302

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2006 ELECTRIC - INTERMEDIATE Approved
07/26/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/25/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
PARTIAL INSPECTION FOR SERVICE ONLY
1. BOND SERVICE RISER RACEWAYS -- NEC 250.92
2. BOND CT ENCLOSURE -- NEC 250.92
3. SERVICE NEUTRALS APPEAR TO BE UNDERSIZED --
NEC 250.24 (B)(1)
4. BONDING JUMPERS TO SERVICE NIPPLES ARE UNDERSIZED
NEC 250.102 (C)
5. TIGHTEN ALL GROUNDING FITTINGS/SET SCREWS -- NEC 110
6. SECURE SERVICE TO STRUCTURE -- NEC 110
7. GROUNDING ELECTRODE CONDUCTOR IS SPLICED INCORRECTLY -- NEC 250.64(C) AND UNDERSIZED PER EXISTING CONDUCTOR SIZE.
8. PROVIDE APPROVED PLANS AS NEEDED -
2 - 750 AS PER PHASE
#1 CU BOND
#2/0 AL NEUT (2)
800 AMP
9. BOND INTERIOR METAL PIPING TO SERVICE -- NEC 250.104