Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. NEED MINIMUM #10 EQUIPMENT GROUND FOR 30 AMP. CKT. NEC 250.122 2. ACORN NOT LISTED FOR 3 - #4 CONNECTIONS - NEC 110.3(B) 3. BOND #235 GAS PIPE -- NEC 250.104(B) 4. IF UFER IS AVAILABLE, BOND IT TO SERVICES NEC 250.50 (BARE #4 HANGING ON STRUCTURE?) 5. IDENTIFY SERVICE NEUTRALS CLOSER TO WEATHERHEAD SO IDENTIFICATION WILL REMAIN AFTER TEP MAKE UP NEC 200 6. PERMIT SAYS "A" AND "B" BUT SERVICES AND UNITS HAVE SEPARATE ADDRESSES -- MAKE SURE PERMIT MATCHES ACTUAL SITUATION. |