Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 07/06/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 2) BOND BOTH SERVICES PER 250.58 AND GAS 250.104 3) RECEIVED CHECK #14132 FOR $108.00 FOR AFTER HOURS INSPECTION |