Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01263
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/13/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAS METER IN FRONT OF SERVICE. 2. NO GROUNDING OTHER THAN WATER BOND. 3. PREVIOUSE ITEMS OF 10/11/06 INSPECTIONS NOT DONE. |
|
| 10/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES #2 -- USE LISTED RISER SUPPORT INSTALL ROOF JACK J-BOX NEEDS TO BE RATED FOR OUTDOOR USE I.D CIRCUIT BREAKERS. |
|
| 07/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DEAD FRONT MISSING TO PANEL 2. ALL CIRCUIT BREAKERS MUST BE OF SAME BRAND AS PANEL 3. SUPPORT CONDUIT RISER PER CODE INSTALL A STRAP BELOW ROOF LINE. 4. SUPPORT 1" CONDUIT BOX MUST BE RAINTITE 5. ROMEX BELOW & ABOVE SERVICE TO OUTSIDE LIGHTS NOT WIRED TO CODE. LIGHTS FIXTURES MUST BE RAINTITE & ROMEX CANNOT BE INSTALLED EXPOSED BELOW ROOF LINE. |