Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/27/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NO MORE THAN 360 DEG. IN A CONDUIT RUN. 2. BOND JUNCTION BOX ENCLOSURE -- 250.148 3. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO -- 406.8 |