Inspection History Details
Inspection Status: Closed
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2007 | ELECTRIC - RECONNECT | Closed | REFERENCE ELEC UPGRADE PERMIT T06EL01261 | |
| 07/03/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RISER HAS TO BE SUPPORTED. 2. GROUND WIRE CUT IN SERVICE & WRONGLY CONNECTED TO WATER. 3. MULTIPLE LUGGING ON BREAKERS & NEUTRAL SLOTS. 4. CONDUITS BELOW SERVICE NOT SUPPORTED REWIRE OPEN 4F BELOW SERVICE. 5. RECEPTACLE BY SERVICE TO BE WEATHERPROOF 6. DEAD FRONT COVER MISSING 7. OUTSIDE WASHER & DRYER RECEPTACLES TO BE WEATHERPROOF SUGGEST YOU HIRE ELECTRICIAN TO CORRECT PROBLEMS POSSIBLY UPGRADE SERVICE. 8. FIX FRONT LIGHT AT PORCH. 9. UF WIRING AT WALL BY COOLER TO BE PROTECTED 10. INSIDE BEDROOMS NEED SMOKE DETECTORS 11. FINISH WIRING AT BEDROOM SWITCHES, OPEN WIRING 12. COVER ALL DEVICES HAVE ELECTRICAL REVIEW INSIDE & OUTSIDE. |