Permit: T06EL01247

Parcel: 133290740


Addresses:

8630 E SHILOH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/10/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/05/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE.
2. DERATING OF CONDUCTORS PER 310.15 IS NEEDED.
3. USE AN APPROVED FITTING WITH LB. CHASE NIPPLE NOT APPROVED.
4. TERMINATE ALL STRANDS OF CONDUCTOR.
5. PLEASE VERIFY BOX FILL FOR SINGLE GANG BELL BOX.
6. RISER HARDWARE TO BE 1/4" MIN.