Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/02/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXPOSE REPAIRS (SPLICES) TO GROUNDING ELECTRODE CONDUCTORS IN RACEWAYS. 2. EXPOSE GUTTERS/CABINETS SO I CAN SEE TERMINATION OF GROUNDING ELECTRODE CONDUCTORS 3. C.T CAN FOR #3837 & 3839 IS BADLY DETERIORATED AND WILL NEED TO BE REPLACED. 4. G.E.C RACEWAY FOR #3819 & 3821 NEEDS TO BE RAN IN A MORE NEAT AND WORKMAN LIKE MANNER. |
|
| 07/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* CORRECTIONS ARE NOT MADE PER CODE -- NEC 250.64 IF NOT CORRECT ON NEXT INSPECTION REINSPECTION FEE WILL BE CHARGED. |