Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 07/05/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* ISOLATE NEUTRALS FROM GROUNDING CONDUCTORS AT SUB-PANEL & BOND EQUIPMENT GROUNDING BUS BAR. |