Permit: T06EL01229

Parcel: 118121050


Addresses:

119 E 24TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06EL01229

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/28/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/26/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND WATER & GAS PIPING, BOTH UNITS
2. INSTALL SEALING LOCKNUTS AT 1/2" LB TERMINATION, CHASE NIPPLE NOT ALLOWED UNLESS LISTED.
3. GROUND RODS DRIVEN AT TO MUCH ANGLE, REINSTALL, CODE ALLOWS 45 DEG. MAX. ANGLE.
4. LIGHT FIXTURE OUTSIDE EAST DOOR IS WIRED IN A HAZARDOUS MANNER, PLEASE REPAIR OR REWIRE TO CODE.