Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/26/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND WATER & GAS PIPING, BOTH UNITS 2. INSTALL SEALING LOCKNUTS AT 1/2" LB TERMINATION, CHASE NIPPLE NOT ALLOWED UNLESS LISTED. 3. GROUND RODS DRIVEN AT TO MUCH ANGLE, REINSTALL, CODE ALLOWS 45 DEG. MAX. ANGLE. 4. LIGHT FIXTURE OUTSIDE EAST DOOR IS WIRED IN A HAZARDOUS MANNER, PLEASE REPAIR OR REWIRE TO CODE. |