Permit: T06EL01213

Parcel: 13005039B

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/18/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
SEE NOTES LAST INSP.
08/15/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
BOND GAS TO BOTH UNITS, REMOVE BOND JUMPER AT GROUND AND NEUT. BUSS & SUB PNLS.

1. NO PERMITS FOR NEW AC'S DISCONNECT BOXES ON ROOF CANNOT BE MOUNTED HOW THEY ARE, CONDUITS FROM PANELS TO AC'S NOT SUPPORTED PROPERLY.
2. SE CABLES FROM SERVICES TO PANELS ARE OUT IN OPEN INSIDE.
3. ALL NEW 3-WIRE RECEPTACLES INSTALLED INSIDE HOWEVER WIRING SYSTEM IS AN UNGROUNDED TYPE.
4. SOME DEVICES INSIDE NOT FINISHED
5. CONDUIT PENETRATIONS THRU ROOF NOT SEALED PROPERLY.
08/14/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND GAS PIPING TO BOTH UNITS ALSO WATER PIPING
2. REMOVE BOND JUMPER AT GROUND & NEUTRAL BUSS.
SUB PANELS.