Permit: T06EL01193

Parcel: 131114240


Addresses:

5639 E 36TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/09/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/07/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
#14 WIRED CIRCUITS (EXISTING WIRING) NEEDS TO BE PROTECTED AT 15 AMPS. MAXIMUM 20 IS TOO LARGE.
07/31/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
1. OUTSIDE J-BOX NEEDS TO BE WEATHERPROOF
2. USE A PLASTIC BUSHING WHERE WIRES COME THRU WALL
3. WIRING INSIDE COMING THRU TO OUTSIDE J-BOX NEEDS TO BE IN A J-BOX ALSO.
4. GROUND J-BOX OUTSIDE
5. STRAP GROUND WIRE TO WALL BELOW SERVICE