Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/07/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* #14 WIRED CIRCUITS (EXISTING WIRING) NEEDS TO BE PROTECTED AT 15 AMPS. MAXIMUM 20 IS TOO LARGE. |
|
| 07/31/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : 1. OUTSIDE J-BOX NEEDS TO BE WEATHERPROOF 2. USE A PLASTIC BUSHING WHERE WIRES COME THRU WALL 3. WIRING INSIDE COMING THRU TO OUTSIDE J-BOX NEEDS TO BE IN A J-BOX ALSO. 4. GROUND J-BOX OUTSIDE 5. STRAP GROUND WIRE TO WALL BELOW SERVICE |