Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/28/2006 | ELECTRIC - SERVICE UPGRADE | Denied | FIELD COLLECTED #108.00 CHECK #1587 AFTER HRS. INSP. 7/28/06 1. INSTALL 2 GROUND RODS 8'X5/8" MIN. AT 6' APART 2. INSTALL CONDUCTORS PER TABLE 310.15 (B) 2A INCREASE WIRE SIZE AT LEAST 1-SIZE UP 3. INSTALL GAS BOND #4 4. INSTALL WATER BOND #4 5. INSTALL ROOF JACK 6. RAISE POINT OF ATTACHMENT HIGHER THAN RISER CONDUIT RESHEDULE INSP. WHEN READY. |
|
| 07/17/2006 | ELECTRIC - SERVICE UPGRADE | Cancelled | CANCELLED PER OWNER CHRISTIAN ORTIZ #440-5680 | |
| 07/17/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |