Permit: T06EL01192

Parcel: 131112000


Addresses:

5852 E 31ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/07/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/28/2006 ELECTRIC - SERVICE UPGRADE Denied FIELD COLLECTED #108.00 CHECK #1587
AFTER HRS. INSP. 7/28/06

1. INSTALL 2 GROUND RODS 8'X5/8" MIN. AT 6' APART
2. INSTALL CONDUCTORS PER TABLE 310.15 (B) 2A
INCREASE WIRE SIZE AT LEAST 1-SIZE UP
3. INSTALL GAS BOND #4
4. INSTALL WATER BOND #4
5. INSTALL ROOF JACK
6. RAISE POINT OF ATTACHMENT HIGHER THAN RISER CONDUIT
RESHEDULE INSP. WHEN READY.
07/17/2006 ELECTRIC - SERVICE UPGRADE Cancelled CANCELLED PER OWNER CHRISTIAN ORTIZ #440-5680
07/17/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*