Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 07/14/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE PROVIDE A 2ND GROUND ROD MIN. 6' SEPARATION INSTALL GROUNDING ELECTRODE CONDUCTOR. 2. FILL UNUSED PORTION OF OPENING. A NEW COMBUSTIBLE PRODUCT IS NEEDED. 3. CORRECTLY IDENTIFY NEUTRAL CONDUCTOR 4. A RISER SUPPORT IS NEEDED BELOW ROOF LINE. 1/4" MIN. HARDWARE. 5. A GAS BOND IS NEEDED 6. CONDUIT TO USE FITTINGS LISTED FOR WET LOCATION. 7. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO. |