Permit: T06EL01160

Parcel: 127040970


Addresses:

5043 E ROSEWOOD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/05/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
TEP RISER TO BE 2" MIN. TO SUPPORT SERVICE CONDUCTOR.
06/22/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN WORKING CLEARANCES 110.26
2. RISER TO BE AS PER TEP REQUIREMENTS.
3. SUPPORT CONDUIT TO SIDE OF PANEL
4. PLEASE LABEL BREAKERS
5. USE AN APPROVED FITTING WITH LB CHASE NIPPLE NOT APPROVED.
6. CONDUCTOR OUT OF WEATHERHEAD TO BE SUNLIGHT RESISTANCE.
7. A BOY BACK SUPPORT MAY BE NEEDED
8. ADDRESS LABEL TO BE PERMANENT LABEL.