Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCKOUT BOTTOM OF PANEL - NEC 110 2. BOND OFFSET NIPPLE PER - NEC 250.92 3. SECURE BELL BOX TO HOUSE - NEC 314 4. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3 5. LABEL ALL CIRCUITS PER - NEC 408.4 6. SECURE EMT WITHIN 3' OF PANEL/BOX CONNECTIONS NEC 358 7. SECURE SERVICE MAST TO HOUSE -- NEC 230 8. NEED TO INSTALL GROUND RODS PER - NEC 250 9. CANNOT SEE INTO METER ENCLOSURE SERVICE ENERGIZED PRIOR TO APPROVALS 10. PROTECT WIRES THROUGH 2" EMT PER NEC 312 & 300 11. SECURE #4 TO BUILDING SURFACE 12. LOCKNUTS FOR OFFSET NIPPLE NOT SEATED UP AGAINST PANEL OR METER ENCLOSURE 13. PROPERLY SECURE PANEL TO HOUSE USE 1/4" HARDWARE NOT PLASTIC ANCHORS. 14. MARK SERVICE DISCONNECT PER NEC 230.70 15. VERIFY GAS BONDING |