Permit: T06EL01158

Parcel: 112031920


Addresses:

3363 N CHRISTMAS AV

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/18/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL OPEN KNOCKOUT BOTTOM OF PANEL - NEC 110
2. BOND OFFSET NIPPLE PER - NEC 250.92
3. SECURE BELL BOX TO HOUSE - NEC 314
4. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3
5. LABEL ALL CIRCUITS PER - NEC 408.4
6. SECURE EMT WITHIN 3' OF PANEL/BOX CONNECTIONS
NEC 358
7. SECURE SERVICE MAST TO HOUSE -- NEC 230
8. NEED TO INSTALL GROUND RODS PER - NEC 250
9. CANNOT SEE INTO METER ENCLOSURE
SERVICE ENERGIZED PRIOR TO APPROVALS
10. PROTECT WIRES THROUGH 2" EMT PER NEC 312 & 300
11. SECURE #4 TO BUILDING SURFACE
12. LOCKNUTS FOR OFFSET NIPPLE NOT SEATED UP AGAINST PANEL OR METER ENCLOSURE
13. PROPERLY SECURE PANEL TO HOUSE
USE 1/4" HARDWARE NOT PLASTIC ANCHORS.
14. MARK SERVICE DISCONNECT PER NEC 230.70
15. VERIFY GAS BONDING