Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T06EL01155
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
06/22/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAS & WATER BOND IS NOT THE CORRECT SIZE SEE TABLE 250-122 2. CONNECT GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO NEUTRAL CONDUCTOR. 3. BRACE CONDUCTORS & SPLIT BOLT CONNECTORS AWAY FROM GUTTER COVER. THEY SHOULD NOT BE MAKING CONTACT WITH THE CUTTER OR COVER. |
|
06/16/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |