Permit: T06EL01155

Parcel: 134161990


Addresses:

7401 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/26/2006 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
06/22/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GAS & WATER BOND IS NOT THE CORRECT SIZE SEE TABLE 250-122
2. CONNECT GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO NEUTRAL CONDUCTOR.
3. BRACE CONDUCTORS & SPLIT BOLT CONNECTORS AWAY FROM GUTTER COVER. THEY SHOULD NOT BE MAKING CONTACT WITH THE CUTTER OR COVER.
06/16/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*