Permit: T06EL01152

Parcel: 140440380

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL01152

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/25/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GARAGE PANEL NEEDS MAIN BREAKER.
2. GARAGE NEEDS GROUNDING ELECTRODE SYSTEM.
3. CONV. RECEPTACLES ALONG WALL NEED TO BE GFCI PROTECTED.
4. INSTALL 1/16" METAL PLATE WHERE STUDS KNOTCHED AT GARAGE FHA-BANG PLATES.
5. EXPOSED THHN (SINGLE CONDUCTORS) ARE NOT AN ALLOWED WIRING METHOD.
6. NEED A QUALIFIED ELECTRICAL CONTRACTOR TO CLEAN UP WIRING IN GARAGE.
7. ROMEX TO BE SECURED WITHIN 8" OF J-BOXES.
8. GARAGE NEEDS PERMIT FOR ELECT.
9. USE MIN. SCH. 80 PVC FOR EXPOSED CONDUIT.
10. INSTALL PROPER CONDUCTORS FOR PANEL FEEDERS.
(NOT ROMEX)