Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GARAGE PANEL NEEDS MAIN BREAKER. 2. GARAGE NEEDS GROUNDING ELECTRODE SYSTEM. 3. CONV. RECEPTACLES ALONG WALL NEED TO BE GFCI PROTECTED. 4. INSTALL 1/16" METAL PLATE WHERE STUDS KNOTCHED AT GARAGE FHA-BANG PLATES. 5. EXPOSED THHN (SINGLE CONDUCTORS) ARE NOT AN ALLOWED WIRING METHOD. 6. NEED A QUALIFIED ELECTRICAL CONTRACTOR TO CLEAN UP WIRING IN GARAGE. 7. ROMEX TO BE SECURED WITHIN 8" OF J-BOXES. 8. GARAGE NEEDS PERMIT FOR ELECT. 9. USE MIN. SCH. 80 PVC FOR EXPOSED CONDUIT. 10. INSTALL PROPER CONDUCTORS FOR PANEL FEEDERS. (NOT ROMEX) |