Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/24/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CLOSE OPENING IN JUNCTION BOX COVER 2. CORRECTLY IDENTIFY CONDUCTOR 3. ONLY ONE CONDUCTOR PER LUG 4. USE APPROVED FITTING WITH LB A CLOSE NIPPLE 5. SEPARATE GROUNDS & NEUTRAL AT JUNCTION BOX |
|
| 06/26/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DO NOT USE WOOD AS CONDUIT SUPPORT. 2. INSTALL PROPER ADDRESS TAG (THIS IS NOT ADEQUATE PER T.E.P) 3. INSTALL WIRING IN A NEAT & WORKMAN LIKE MANNER (#4 GROUNDING ELECTRODE CONDUCTOR SHOULD BE STRAIGTENED). 4. INSTALL BONDING BUSHING ON 1 1/2" CONDUIT AT NEW SERVICE PANEL. 5. WATER PIPE CLAMP NEEDS TO BE BRASS. 6. IDENTIFY NEUTRAL CONDUCTOR WHITE NOT YELLOW 7. OLD EQUIP. WILL NEED TO BE REPLACED. |