Permit: T06EL01145

Parcel: 122182240

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/12/2007 ELECTRIC - INTERMEDIATE Approved
12/05/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/01/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. TIGHTEN LOOSE FITTINGS
2. FINISH PREVIOUS ITEM 3 & 4
08/25/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CAN'T HAVE NEUTRAL TO ENCLOSURE BOND IN SUB-PANELS
2. AT SERVICE TERMINATE EQUIPMENT GROUNDS AT FACTORY PROVIDED LOCATION AND MAKE UP CONDUCTORS SO YOU DON'T HAVE ALL THAT EXTRA WIRING (NEAT AND WORKMAN LIKE).
3. TIGHTEN ALL CONNECTIONS AND MAKE SURE INSULATION IS NOT UNDER TERMINATION.
4. PROVIDE ACCESS TO ROOMS BEHIND SERVICE AND MAKE SURE ALL GAS AND WATER PIPES ARE BONDED TO SERVICE.
08/22/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. RISER HARDWARE TO BE 1/4" MINIMUM
2. CHASE NIPPLE NOT AN APPROVED FITTING FOR USE
WITH LB
3. CANNOT TRIM CONDUCTORS USE ALL STRANDS
4. FINISH SUPPORTING CONDUITS
5. PROTECT CONDUCTORS AT FITTING 300.4
6. TIGHTEN LOOSE FITTINGS
7. USE GROUND CLAMP AS PER MANUFACTURERS INSTRUCTIONS.