Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
| 12/05/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 12/01/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. TIGHTEN LOOSE FITTINGS 2. FINISH PREVIOUS ITEM 3 & 4 |
|
| 08/25/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CAN'T HAVE NEUTRAL TO ENCLOSURE BOND IN SUB-PANELS 2. AT SERVICE TERMINATE EQUIPMENT GROUNDS AT FACTORY PROVIDED LOCATION AND MAKE UP CONDUCTORS SO YOU DON'T HAVE ALL THAT EXTRA WIRING (NEAT AND WORKMAN LIKE). 3. TIGHTEN ALL CONNECTIONS AND MAKE SURE INSULATION IS NOT UNDER TERMINATION. 4. PROVIDE ACCESS TO ROOMS BEHIND SERVICE AND MAKE SURE ALL GAS AND WATER PIPES ARE BONDED TO SERVICE. |
|
| 08/22/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. RISER HARDWARE TO BE 1/4" MINIMUM 2. CHASE NIPPLE NOT AN APPROVED FITTING FOR USE WITH LB 3. CANNOT TRIM CONDUCTORS USE ALL STRANDS 4. FINISH SUPPORTING CONDUITS 5. PROTECT CONDUCTORS AT FITTING 300.4 6. TIGHTEN LOOSE FITTINGS 7. USE GROUND CLAMP AS PER MANUFACTURERS INSTRUCTIONS. |