Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CORRECTIONS NOT MADE 2. REINSPECTION FEE NOT PAIN FROM LAST INSPECTION - BEFORE CALLING AGAIN TAKE CARE OF BOTH THESE CORRECTIONS OR ANOTHER REINSPECTION FEE WILL BE CHARGED. |
|
| 06/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1) THE MAIN GROUNDING ELECTRODE GOING INTO THE CT CAN AT THE SERVICE HAS BEEN CUT AND WILL NEED TO BE PROPERLY REPAIRED BEFORE POWER CAN BE APPROVED. YOU ALSO HAVE SEVERAL OTHER SERVICES WITH THE SAME PROBLEM. HAVE ELECTRICAL CONTRACTOR TAKE OUT A REPAIR PERMIT-REPAIRS MUST BE MADE PER NEC 250.64 |
|
| 06/16/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* MAIN GROUNDING ELECTRODE CONDUCTOR HAS BEEN CUT AT SERVICE AND WILL NEED TO BE REPAIRED. |