Permit: T06EL01127

Parcel: 123130140


Addresses:

2328 N HAMPTON ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL01127

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED SEALING TYPE LOCKNUT FOR RACEWAY ENTRY INTO SERVICE ABOVE LIVE PARTS.
2. NEED RAINTYPE J-BOX ENCLOSURE FOR EXTERIOR USE AND ALL OPEN HOLES CLOSED OFF.
3. IDENTIFY NEUTRALS.
4. MAKE SURE NEUTRAL IS NOT BONDED TO ENCLOSURE IN SUB-PANEL GROUNDS AND NEUTRALS MUST "FLOAT".
06/20/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CALL AFTER ENERGIZED AND COMPLETE
06/16/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. PROVIDE PROPER WORKING NEC 110.33A
2. SERVICE CONDUCTORS NEED MINIMUM 10' OFF GROUND CLEARANCE NEC 230.24 (B)