Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01127
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED SEALING TYPE LOCKNUT FOR RACEWAY ENTRY INTO SERVICE ABOVE LIVE PARTS. 2. NEED RAINTYPE J-BOX ENCLOSURE FOR EXTERIOR USE AND ALL OPEN HOLES CLOSED OFF. 3. IDENTIFY NEUTRALS. 4. MAKE SURE NEUTRAL IS NOT BONDED TO ENCLOSURE IN SUB-PANEL GROUNDS AND NEUTRALS MUST "FLOAT". |
|
06/20/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CALL AFTER ENERGIZED AND COMPLETE |
|
06/16/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. PROVIDE PROPER WORKING NEC 110.33A 2. SERVICE CONDUCTORS NEED MINIMUM 10' OFF GROUND CLEARANCE NEC 230.24 (B) |