Permit: T06EL01120

Parcel: 121040150

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/09/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) CALL IN FOR A/C AFTER POWER IS ON
09/29/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
WAITING ON CLEARANCE FROM DAN QUINN
09/28/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/07/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO FURTHER INSPECTIONS UNTIL PERMITTING ISSUES RESOLVED WITH HOUSING INSPECTOR DAVE COX 954-0155
06/27/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/20/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/16/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE.
2. A PERMANENT METAL ADDRESS LABEL IS NEEDED
3. RISER HARDWARE TO BE 1/4" MINIMUM.
4. PLEASE VERIFY GAS & WATER BONDING.
5. THIS IS AN UNOCCUPIED STRUCTURE MAKE ALL CONNECTIONS TO SERVICE BREAKERS.
6. NEED ACCESS TO INTERIOR TO INSPECT JUNCTION BOX FOR NEW NM CABLES.
7. IS SUB-PANEL IN CARPORT NEW?