Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/29/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 09/28/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR AT SERVICE. 2. INTERIOR WIRING TO BE ADDED TO COMBUSTION PERMIT #T06CM05147 3. BOND TO BE COLD WATER SIDE OF WATER HEATER |
|
| 07/07/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/27/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) NEED A LICENSED ELECTRICAL CONTRACTOR TO PERFORM WORK 2) HOUSING INSPECTOR TO DETERMINE IN WALL WORK DONE WITHOUT PERMITS 3) FINISH PREVIOUS ITEMS |
|
| 06/20/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1 WHERE IS SPLICE CONNECTION FOR ALL CIRCUITS-JUNCTION BOX (OLD PANEL) ONLY HS 4 CIRCUITS. IF NEW WIRING WAS DONE PLEASE VERIFY PERMIT FOR IN WALL INSPECTIONS. 2. BREAKER AMPACITY FOR #8 NM CABLE TO BE AS PER 334.80 3. PLEASE VERIFY GAS BONDING. 4. MAINTAIN WORKING CLEARANCES 110.26 |
|
| 06/16/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |