Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/07/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO INSTALL ROOF JACK & SEAL IT. 2. USE A ROMEX CONNECTOR AT BOTTOM OF PANEL WHERE GROUND WIRE COMES INTO BOTTOM ENTRY. 3. WHERE LB CONDUIT ENTERS EAST WALL PF PANEL MUST USE A CLOSED NIPPLE WITH LOCKNUTS ATTACHED TO PANEL WALL AND ONE OF THE LOCKNUTS MUST BE A SEALING LOCKNUT BECAUSE PENETRATION IS MADE ABOVE BUS LINE. 4. NEED TO SECURE BOND WIRE FROM EVE AT ROOF DOWN WALL TO GAS & WATER ONE. |