Permit: T06EL01109

Parcel: 112030920


Addresses:

2910 E RICHARDS ROW

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/21/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/07/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO INSTALL ROOF JACK & SEAL IT.
2. USE A ROMEX CONNECTOR AT BOTTOM OF PANEL WHERE GROUND WIRE COMES INTO BOTTOM ENTRY.
3. WHERE LB CONDUIT ENTERS EAST WALL PF PANEL MUST USE A CLOSED NIPPLE WITH LOCKNUTS ATTACHED TO PANEL WALL AND ONE OF THE LOCKNUTS MUST BE A SEALING LOCKNUT BECAUSE PENETRATION IS MADE ABOVE BUS LINE.
4. NEED TO SECURE BOND WIRE FROM EVE AT ROOF DOWN WALL TO GAS & WATER ONE.