Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/05/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEM #8 NEW PERMIT |
|
| 09/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE AN APPROVED FITTING WITH LB. CHASE NIPPLE NOT APPROVED 110.3 2. INSTALL ALL STRANDS UNDER TERMINAL LUG. 3. USE APPROVED FITTINGS WITH CARFLEX -- 110.3 4. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 5. CABLES TO BE SECURED TO BOX -- 312.5 6. PLEASE VERIFY CONNECTIONS OF NEW NM CABLES 7. VERIFY NEUTRAL PHASE LOADS DUE TO PANEL CIRCUITING. 8. PREVIOUS ISSUES WITH NEW WIRING NOT RESOLVED. |
|
| 08/10/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECALL AFTER CROSS OVER 2) A SEPERATE PERMIT FOR NEW WIRING IS NEEDED |
|
| 07/20/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PLEASE COMPLETE #1 & 2 OF PREVIOUS ITEMS. |
|
| 07/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NO ANSWER AT DOOR -- PLEASE LOCK UP DOGS |
|