Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL01089

Parcel: 126061880


Addresses:

705 N IRVING CI

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
10/23/2006 ELECTRIC - CABLE DROP Approved
10/05/2006 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
08/10/2006 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
07/20/2006 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
07/13/2006 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
07/10/2006 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. PLEASE VERIFY PERMIT FOR NEW WIRING IN FRONT AND CANS.
2. MAINTAIN WORKING CLEARANCE IN FRONT OF PANEL 110.26
3. RISER HARDWARE TO BE 1/4" MINIMUM
4. PLEASE VERIFY 2ND GROUND ROD AND WATER BOND CONNECTION.