Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01077
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BONDING CONDUCTOR FOR SERVICE NIPPLE IS UNDERSIZED NEC 250.102 (C) 2. IDENTIFY SERVICE DISCONNECT - NEC 230.70 (B) 3. DRIVE GROUND RODS FLUSH - NEC 250.53 (6) 4. REMOVE PAINT AT GAS BOND CLAMP - NEC 250.12 5. BOND ALL METAL PIPE SYSTEMS TO SERVICE - NEC 250.104 |