06/08/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. BONDING CONDUCTOR FOR SERVICE NIPPLE IS UNDERSIZED NEC 250.102 (C)
2. IDENTIFY SERVICE DISCONNECT - NEC 230.70 (B)
3. DRIVE GROUND RODS FLUSH - NEC 250.53 (6)
4. REMOVE PAINT AT GAS BOND CLAMP - NEC 250.12