Permit: T06EL01074

Parcel: 125076300


Addresses:

531 N NORRIS AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/06/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/30/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
533 & 531
1. INSTALL ADDRESS ON SERVICE.
2. IDENTIFY UNITS AT SERVICE DISCONNECTS.
3. GROUNDING ELECTRODE NEEDS TO BE SECURED TO STRUCTURE AND BURIED TO GROUND RODS.
4. GROUND RODS NEED TO BE MINIMUM 6' APART.
5. CLAMPS FOR RODS NEED TO BE USED WITH WIRE SIZE LISTED.
6. USE PROPER CLAMP FOR UFER BOND WIRE/USE AS LISTED
7. BOND EACH UNIT GAS AND WATER PIPES TO SERVICE.
8. MAST IS NOT BONDED (MYERS HUB NMOT APPROVED FOR LINE SIDE BONDING).
9. NEED TO FILL OUT WAIVER FORM WITH CITY FOR OVERHEAD SERVICE.
10. GROUNDS AND NEUTRAL MUST BE SEPARATED IN SUB-PANELS AND UNUSED OPENINGS FILLED.