Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/19/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAINTAIN CLEARANCES OF SERVICE CONDUCTORS PER 680.1 EDGE OF POOL 2. MAINTAIN WORKING CLEARANCES PER 110.26 3. ENTRANCES ABOVE CURRENT CARRING PART TO USE APPROVED SEALING DEVICES. 4. BONDING JUMPER TO BE SIZED PER 250.122 5. PLEASE CLEAN SURFACE UNDER GROUND BAR 250.12 |