Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/21/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/19/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN CLEARANCES OF SERVICE CONDUCTORS PER 680.1 EDGE OF POOL
2. MAINTAIN WORKING CLEARANCES PER 110.26
3. ENTRANCES ABOVE CURRENT CARRING PART TO USE APPROVED SEALING DEVICES.
4. BONDING JUMPER TO BE SIZED PER 250.122
5. PLEASE CLEAN SURFACE UNDER GROUND BAR 250.12