Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T06EL01056
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 06/28/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1 INSTALL 2 GROUND RODS 6' APAPRT 2) BOND WATER PIPING 3) SUPPORT RISER BELOW ROOF OVER HANG-USE MIN. 1/4" BOLTS 4) INSTALL PERMANENT ADDRESS LABEL |