Permit: T06EL01051

Parcel: 140232820


Addresses:

6226 S EUCLID AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/24/2006 ELECTRIC - FINAL Approved
07/18/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ADD SERVICE UPGRADE TO THIS PERMIT.
2. RISER CONDUIT NOT INSTALLED PER TEP SPECS, SEE OR CONSULT WITH TEP TECH FOR YOUR AREA.
3. 2 GROUND RODS REQUIRED 6' MIN. APART
4. INSTALL PERMANENT ADDRESS LABEL ON SERVICE.
5. SEE NOTE #5
06/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MUST COMPLY WITH NOTE #5 LAST INSPECTION.
06/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COOLER WIRING EXPOSED, NOT PER CODE.
2. WIRING IN BACK BY WATER HTR. NOT PER CODE, EXPOSED ROMEX, INDOOR RATED ELECTRICAL PANEL & DISCONNECT.
3. EXTENSION CORDS NOT APPROVED TO SUPPLY POWER TO SMALL TRAILER ATTACHED TO BUILDING.
4. WIRING AT SMALL STORAGE ROOM NOT TO CODE.
5. ELECTRIC SERVICE & WIRING NEEDS TO BE BROUGHT UP TO CODE, IF UPGRADED PERMIT REQUIRED.
6. INSIDE WIRING NOT TO CODE, INSTALL SMOKE DETECTORS, LIGHT FIXTURES, COVER PLATES, MUST BE INSTALLED.