Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. I.D CIRCUIT BREAKERS. 2. CHASE NIPPLES NOT ALLOWED FOR TERMINATION INTO SERVICE ENCLOSURE - USE CLOSE NIPPLES WITH LOCKNUTS BOTH ENDS - USE BOND BUSHINGS AT CONCENTRIC KO'S. 2. SUPPORT CONDUITS 3/4" & 1" 3. SUPPORT RISER CONDUIT TO STRUCTURE BELOW ROOF OVERHANG. |