Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 06/05/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NOTES: CONTR. ALSO INSTALLED 5 NEW RECEPTS, LIGHT AND WIRING PER CUSTOMER. THESE ITEMS ARE TO BE ADDED TO PERMIT, BEFORE FINAL CAN BE APPROVED |
|
| 06/02/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: CONTRACTOR INSTALLED SEPARATE GROUND - NOT ALLOWED, GROUND MUST BE IN SAME CABLE SHEATH OR RACEWAY AS FEEDER CONDUCTORS, ALSO NOT COLOR CODED. |
|
| 05/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* #1 DRIVE GROUND RODS TO BELOW GRADE TO AVOID TRIP HAZARD. #2 1/2 EMT CONDUIT AT ENTRY TO TOP OF J-BOX CAN SEE DAYLIGHT THRU YELLOW CEILING LOCKNUT. #3 NEW SUB-PANEL RUN A GROUND IN WITH THE NEW FEED AND ISOLATE NEUTRALS & GROUNDS AT SUB-PANEL IN LAUNDRY ROOM. |