Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01020
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2006 | ELECTRIC - FINAL | Approved | ||
08/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY NEW FEEDER IN SERVICE PANEL NEC 408.4 2. A GROUNDING ELECTRODE IS REQUIRED FOR NEW PANEL IN LAUNDRY - NEC 250.32 3. SECURE NEW PANEL TO WALL -- NEC 110.13 4. HAVE 14 GA WIRE ON 20 AMP BREAKER (LIGHTING) NEC 310 5. NEW PANEL DOES NOT HAVE PROPER ENTRY CLEARANCE NEC 110.26 OK TO COVER TRENCH |