Permit: T06EL01016

Parcel: 106060690


Addresses:

1222 W PELAAR ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/02/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ELECT. CONTRACTOR: ALUM SER ENTERING SUB-PANEL INSDIE TO HAVE CLAMP OR BUSHING - SEPARATE GRD/NEUT.
2. OWNER: GROUNDS & NEUTRALS TO BE SEPARATED IN SUB-PANEL.
3. HOLES WHERE WIRING ENTERS SUB-PANEL TO HAVE PLASTIC BUSHINGS & SEAL HOLES IN SUB-PANEL.