Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/28/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/18/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CALL FOR FINAL WHEN CUT OVER IS COMPLETED
07/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BOND INTERIOR METAL PIPING SYSTEMS PER N.E.C ART. 250
(THIS INCLUDES ABANDONED GAS PIPING)
SECURE #4 COPPER CONDUCTOR TO SLAB OR STRUCTURE
06/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GROUND RODS FLUSH & GAS BOND - GAS TO BE REMOVED.
IF GAS METER IS ON SITE & HOOKED UP EVEN IF NOT ON, IT HAS TO BE BONDED. WHY HASN'T NEW WIRING FROM NEW LOCATION OF SERVICE BEEN STARTED TO OLD SERVICE.
06/29/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
* INSTALL GAS BOND (#4 CONDUCTOR)
* DRIVE RODS FLUSH OR BELOW FINISHED GRADE
CLEARANCE TO TEP IS SUBJECT TO THE ABOVE LISTED CORRECTIONS.