Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01003
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER TIE IN 2) OK LOAD CALC'S |
|
| 10/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLY WITH NOTE #1, #2, #3, #4 |
|
| 05/31/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NOTES: 1. BOND WATER & GAS PIPING, VERIFY EACH UNIT BONDED PER NEC 2. NEED TO VERIFY WIRING METHODS FOR NEW FEEDERS BEHIND METER/DISCONNECTS. 3. G-UNITS WITH 60A MAINS ON 200 AMP. SERVICE - PROVIDE APPROVED LOAD CALC'S. 4. FEEDERS MUST HAVE AT LEAST 1/4" OF CABLE SHEATH INSIDE CABINET OR ENCLOSURE PER NEC. 5. USE MIN. 1/4" BOLTS TO SUPPORT RISER CONDUIT. |